Fire Detection & Alarm
Detector coverage: smoke ≈ 60 m², heat ≈ 20 m² (ceiling ≤ 7.5 m)Battery Ah = (Is x 24 h + Ia x 0.5 h) x 1.25Example: Is 0.4 A, Ia 2 A → 13.25 Ah
Links
Calculators: Fire Detection & Alarm calculator
Catalogue categories: Fire Alarm, Detectors, Hooters & Strobes