Design rules for Fire Suppression (Gas & Special Hazards)
TopicsOpen
Home / Knowledge hub / Fire Suppression (Gas & Special Hazards) / Design rules of thumb & formulas
Fire Suppression (Gas & Special Hazards)
Halocarbon: W = (V/S)·(C/(100−C)), S = k1 + k2·TInert gas: X = 2.303·(Vs/S)·log10(100/(100−C))- Vent area for over-pressure per agent maker
Links