Design rules for Electrical

TopicsOpen

Home / Knowledge hub / Electrical / Design rules of thumb & formulas

Electrical

  • Current (3-phase): I = P / (√3 · V · pf)
  • Voltage drop: VD = √3 · I · L · (R cosφ + X sinφ); keep ≤ 3–5%
  • Transformer: kVA = kW / pf x diversity
  • Earth rod: R = ρ / (2πL) · ln(4L/d)
  • Lighting: N = E · A / (Φ · UF · MF)
  • APFC: kVAr = kW (tanφ1 − tanφ2)
  • DG: kVA = load kW / 0.8, checked for largest motor start

Products for this system

Cable size calculatorElectrical design

Products and services

Standards cited by number for reference; verify designs with a qualified engineer.