Engineering hub
Engineering Hub: System Design, Drawings & BOQ
Enter the duty, or describe any requirement and attach the drawing. AutoCAD, PDF, a spreadsheet or a photograph is accepted. The desk sizes what it can from NBC 2016 Part 4, IS 15105, IS 3844, IS 13039, TAC, NFPA 13, NFPA 20, IS 732, IS 3043, IS 2189, ISHRAE and ASHRAE 62.1, draws the P&ID or single-line diagram, the scaled plan, both elevations, section A-A and the isometric, and writes the bill. A PEB shed takes length, width, eave, bay, slope, basic wind speed, crane and cladding, and draws the framing plan, the anchor bolt plan, both elevations, section A-A and a rotatable 3D model. Fire suppression and fire detection sit under Fire protection, not as a separate project type. A mark you add on the sheet is saved with the download. A licensed engineer still stamps the issue.
Choose project type
HVAC is selected. The subcategories for this type are under this list. The drawing and the bill further down are the existing type page. A catalogue price is used when it matches. Otherwise a published Indian rate plus 20% is shown with its source. Erection is 10% of that system's materials, testing 2%, and transport 3%.
Subcategories
Each subcategory has its own design basis, calculation, drawings, bill and quotation.
Drawing is listening

Rev A
SHEET 1 OF 6
Calculation
| Part | Formula | Working | Result | Standard |
|---|---|---|---|---|
| Cooling load | TR = (area per floor × floors) ÷ m² per TR | 2,000 m² × 2 floors ÷ 22 m²/TR. | 182 TR | ISHRAE / ASHRAE 62.1 |
| Supply air | The larger of 400 cfm/TR and outdoor air | Coil 72,800 cfm. Outdoor air 200 people × 10 L/s + 0.3 L/s·m² = 6,781 cfm. | 72,800 cfm | ASHRAE 62.1 / NBC Part 8 |
Design basis
| Part | Specification | Standard |
|---|---|---|
| air handling unit 60000 | 182 TR from 2,000 m² × 2 floors at the same m²/TR as the cooling tool. Supply 72,800 cfm. 1 × 60,000 cfm = 60,000 cfm, within about 10–20% above the required air. | ISHRAE / ASHRAE 62.1 / NBC Part 8 |
| chiller 200 | 182 TR from 2,000 m² × 2 floors. 1 × 200 TR is the next standard chiller at or above that load. | ASHRAE / ISHRAE |
| GI sheet 24 gauge per kg | Duct sheet area 345.6 m² is an allowance, not a measured take-off: 240 lengths × 1.2 m × 1.2 m girth. 24 gauge is 0.60 mm, 4.71 kg/m². Weight = duct area × sheet weight = 1,628 kg. Priced per kg of that gauge. | SMACNA |
| fire damper | Fire and volume dampers. The wall schedule fixes the real count. | NBC Part 8 |
| insulation nitrile | Chilled-pipe insulation, 48 m. The catalogue price is a 2 m tube, so the rate is that price divided by 2. | NBC Part 8 |
| Duct elbow | 346 m of duct. One 90° elbow about every 8 m, so the fittings stay under the duct-sheet allowance. 400 mm is the catalogue size until the duct drawing fixes the throat. | SMACNA |
| Duct tee | Branch tees off the same duct allowance. | SMACNA |
| Duct reducer | Reducers off the same duct allowance. | SMACNA |
| Volume damper | Volume dampers in the branches. Fire dampers are already on the bill and are not counted again. 400 mm is the catalogue size. | NBC Part 8 |
| Diffuser | One 600×600 mm square diffuser or grille about every 20 m² of the floor. 600×600 is the published size used as the allowance. | ISHRAE |
| Duct hanger | GI duct clamps from 345.6 m² of sheet, one about every 3 m². The published piece is a 190 mm round duct clamp. | SMACNA |
| Sealant | Duct joints on 345.6 m². One cartridge about every 15 m². | Site practice |
| CHW valve | Chilled-water isolation on a 182 TR plant. Supply, return, bypass and drain. Bore 150 NB is the allowance for that load. | API 600 |
| CHW strainer | Strainer on the chiller return. | Site practice |
| CHW check | Non-return on the two CHW pumps or the bypass pair. | API 594 |
| CHW flange | Two flanges on each of the four CHW valves. | ASME B16.5 |
| CHW gasket | One gasket on each CHW flange. | ASME B16.20 |
| Bolt | Eight bolts on each of four CHW valve pairs. Calc 32 bolts | Billed 1 lot of 100. M16 × 60 mm, grade 8.8. The catalogue price is a box or lot, so it is not multiplied by the bolt count. | ISO 4014 |
| Pressure gauge | CHW supply and return. 4 inch dial, 0–10 kg/cm². | IS 3624 |
| Hanger | CHW pipe hanger allowance, 12 m a floor. One hanger about every 3 m, 8 clamps, 150 mm to match the line. Price on request unless the catalogue has this bore. An 80 mm clamp is not used on a different line. | Site practice |
| Testing | HVAC testing and commissioning. 2% of this system's material subtotal, ex-GST. GST 18% is added on this allowance. | Site practice |
| Erection | HVAC erection and installation labour. 10% of this system's material subtotal, ex-GST. GST 18% is added on this allowance. | Site practice |
| Transport | HVAC transport and freight. 3% of this system's material subtotal, ex-GST. GST 18% is added on this allowance. | Site practice |
HVAC BOQ
Proactive Industrial Private LimitedGSTIN: 24AAQCP1475R1ZLRegistered office: C-119, Siddhivinayak Business Tower, Makarba, Sarkhej, Ahmedabad, Gujarat 380051Branch offices: Vadodara | Padal (Kheda) | BharuchSupply
air handling unit 60000
182 TR from 2,000 m² × 2 floors at the same m²/TR as the cooling tool. Supply 72,800 cfm. 1 × 60,000 cfm = 60,000 cfm, within about 10–20% above the required air. · ISHRAE / ASHRAE 62.1 / NBC Part 8
1 no. × —
GST —
Amount —
chiller 200
182 TR from 2,000 m² × 2 floors. 1 × 200 TR is the next standard chiller at or above that load. · ASHRAE / ISHRAE
1 no. × —
GST —
Amount —
GI sheet 24 gauge per kg
Duct sheet area 345.6 m² is an allowance, not a measured take-off: 240 lengths × 1.2 m × 1.2 m girth. 24 gauge is 0.60 mm, 4.71 kg/m². Weight = duct area × sheet weight = 1,628 kg. Priced per kg of that gauge. · SMACNA
1628 kg × —
GST —
Amount —
fire damper
Fire and volume dampers. The wall schedule fixes the real count. · NBC Part 8
8 no. × —
GST —
Amount —
insulation nitrile
Chilled-pipe insulation, 48 m. The catalogue price is a 2 m tube, so the rate is that price divided by 2. · NBC Part 8
48 m × —
GST —
Amount —
duct fitting 90 elbow 400 mm
346 m of duct. One 90° elbow about every 8 m, so the fittings stay under the duct-sheet allowance. 400 mm is the catalogue size until the duct drawing fixes the throat. · SMACNA
44 no. × —
GST —
Amount —
duct fitting tee 400 mm
Branch tees off the same duct allowance. · SMACNA
22 no. × —
GST —
Amount —
duct fitting reducer 400 mm
Reducers off the same duct allowance. · SMACNA
15 no. × —
GST —
Amount —
volume damper 400 mm
Volume dampers in the branches. Fire dampers are already on the bill and are not counted again. 400 mm is the catalogue size. · NBC Part 8
5 no. × —
GST —
Amount —
square diffuser grille
One 600×600 mm square diffuser or grille about every 20 m² of the floor. 600×600 is the published size used as the allowance. · ISHRAE
100 no. × —
GST —
Amount —
duct hanger
GI duct clamps from 345.6 m² of sheet, one about every 3 m². The published piece is a 190 mm round duct clamp. · SMACNA
116 no. × —
GST —
Amount —
silicone sealant 280 ml
Duct joints on 345.6 m². One cartridge about every 15 m². · Site practice
24 no. × —
GST —
Amount —
gate valve 150 NB
Chilled-water isolation on a 182 TR plant. Supply, return, bypass and drain. Bore 150 NB is the allowance for that load. · API 600
4 no. × —
GST —
Amount —
Y strainer 150 NB
Strainer on the chiller return. · Site practice
1 no. × —
GST —
Amount —
check valve 150 NB
Non-return on the two CHW pumps or the bypass pair. · API 594
2 no. × —
GST —
Amount —
flange 150 NB class 150 A105
Two flanges on each of the four CHW valves. · ASME B16.5
8 no. × —
GST —
Amount —
spiral wound gasket 150 NB class 150
One gasket on each CHW flange. · ASME B16.20
8 no. × —
GST —
Amount —
hex bolt M16 60 mm grade 8.8
Eight bolts on each of four CHW valve pairs. Calc 32 bolts | Billed 1 lot of 100. M16 × 60 mm, grade 8.8. The catalogue price is a box or lot, so it is not multiplied by the bolt count. · ISO 4014
1 lot × —
GST —
Amount —
pressure gauge
CHW supply and return. 4 inch dial, 0–10 kg/cm². · IS 3624
2 no. × —
GST —
Amount —
GI pipe clamp 150 mm
CHW pipe hanger allowance, 12 m a floor. One hanger about every 3 m, 8 clamps, 150 mm to match the line. Price on request unless the catalogue has this bore. An 80 mm clamp is not used on a different line. · Site practice
8 no. × —
GST —
Amount —
transport to site
HVAC transport and freight. 3% of this system's material subtotal, ex-GST. GST 18% is added on this allowance. · Site practice
1 lot × —
GST —
Amount —
Supply subtotal—
Installation
testing and commissioning
HVAC testing and commissioning. 2% of this system's material subtotal, ex-GST. GST 18% is added on this allowance. · Site practice
1 lot × —
GST —
Amount —
erection and labour
HVAC erection and installation labour. 10% of this system's material subtotal, ex-GST. GST 18% is added on this allowance. · Site practice
1 lot × —
GST —
Amount —
Installation subtotal—
GST —
Grand total —
Supply is the material and the transport. Installation is erection, testing and commissioning, and the other site services. Each section has its own ex-GST subtotal. GST and the grand total follow. A catalogue match is used when the catalogue has a price. Where it does not, the rate is a published Indian marketplace or maker price plus 20%, and the source is on the line. Every material rate is ex-GST, and GST at 18% is added on it. A published price that already included GST is converted to the ex-GST figure and 18% is shown separately. Erection and installation labour is 10% of that system's material subtotal, testing and commissioning 2%, and transport 3%, with GST at 18% on those allowances.
Freight
Ahmedabad to Vadodara · about 131 km · chargeable 150 kg
Freight ₹1,800 ex-GST · GST ₹324 · Payable ₹2,124
Road part-load from the pincode. Chargeable weight is the higher of actual kg and 300 kg per cubic metre. Confirm the truck before a PO.
- 2,000 m² is the area of one floor, 2 floors, 8 m height. Sprinkler heads, sprinkler branch pipe and smoke detectors are that floor counted again on every floor. The sprinkler pump stays on the remote design area.
- Prices on the quotation are ex-GST. A catalogue match is used first. Where the catalogue has no price, a published Indian rate plus 20% is used and the source is on the line. GST at 18% is added on every material line. A price the source already quoted including GST is converted to the ex-GST rate and 18% is shown separately. Erection and installation labour is 10% of that system's material subtotal, testing and commissioning 2%, and transport 3%. GST 18% is added on those allowances.
- Standards cited on this desk: NBC 2016 Part 4, IS 15105, IS 3844, IS 13039, TAC, NFPA 13, NFPA 20, IS 732, IS 3043, IS 2189, ISHRAE and ASHRAE 62.1.
Get this designed & installed by us
Statutory
- This is an enquiry BOQ, not a sanctioned design. A licensed consultant stamps the drawing before construction.
- The heat load, fresh-air schedule and fire-damper schedule are part of the design. ECBC applies to a commercial building above the state threshold. A licensed MEP consultant stamps the drawing before construction.